COLUMNAS DE TABIQUE MORTEROS UTILIZADOS EL MORTERO TENDRA UNA RESISTENCIA NOMINAL A LA COMPRESION DE POR LO M COLUMAS CORTAS RELACION DE ESBELTEZ H/a1 < O = 12 (COLUMNA CORTA) H = ALTURA DE LA COLUMNA a1 = LADO DE LA COLUMNA COLUMAS LARGAS RELACION DE ESBELTEZ H/a1 > 12 (COLUMNA LARGA) H = ALTURA DE LA COLUMNA a1 = LADO DE LA COLUMNA FORMULA DE DISEÑO P = Af*b P = CARGA AXIAL ADMISIBLE A = AREA BRUTA DE LA SECCION TRANSVERSAL f*b = RESISTENCIA NOMINAL DE DISEÑO DEL MORTERO EN COMPRESION FACTOR DE REDUCCION I 1.00 - 0.15 3.16 125.00 I-A 1.00 0.25 - 3.44 125.00 II 1.00 - 0.40 3.85 75.00 II-A 1.00 0.75 - 4.81 75.00 III 1.00 - 1.00 5.50 40.00 FACTORES DE CARGA A 1.4 B 1.5 SECCIONES DE COLUMNAS DE TABIQUE SECCION LADO CORTO LADO LARGO 21X28 21.00 28.00 28X28 28.00 28.00 LA RESISTENCIA OBTENIDA CON LA FORMULA DE DISEÑO SERA AFECTADA POR EL (Fr), QUE SE CONSIDERARA IGUAL A 0.7 PARA LAS COLUMNAS CORTAS Y DE 0. PROPORCIONAMIENTOS RECOMENDADOS PARA MORTERO ESTRUCTURALES (GDF, 2002a) TIPO DE MORTERO PARTES DE CEMENTO PARTES DE CEMENTO DE ALBAÑILERI PARTES DE CAL PARTES DE ARENA RESISTENCI A A LA COMPRESION
Transcript
Page 1: .COLUMNAS TABIQUE(1)

COLUMNAS DE TABIQUEMORTEROS UTILIZADOS

COLUMAS CORTASRELACION DE ESBELTEZ

H/a1 < O = 12 (COLUMNA CORTA)

H = ALTURA DE LA COLUMNAa1 = LADO DE LA COLUMNA

COLUMAS LARGASRELACION DE ESBELTEZ

H/a1 > 12 (COLUMNA LARGA)

H = ALTURA DE LA COLUMNAa1 = LADO DE LA COLUMNA

FORMULA DE DISEÑOP = Af*b

P = CARGA AXIAL ADMISIBLEA = AREA BRUTA DE LA SECCION TRANSVERSALf*b = RESISTENCIA NOMINAL DE DISEÑO DEL MORTERO EN COMPRESION

FACTOR DE REDUCCION

I 1.00 - 0.15 3.16 125.00 I-A 1.00 0.25 - 3.44 125.00 II 1.00 - 0.40 3.85 75.00

II-A 1.00 0.75 - 4.81 75.00 III 1.00 - 1.00 5.50 40.00

FACTORES DE CARGAA 1.4B 1.5

SECCIONES DE COLUMNAS DE TABIQUESECCIONLADO CORTOLADO LARGO21X28 21.00 28.00 28X28 28.00 28.00

EL MORTERO TENDRA UNA RESISTENCIA NOMINAL A LA COMPRESION DE POR LO MENOS 15 KG./CM2.

LA RESISTENCIA OBTENIDA CON LA FORMULA DE DISEÑO SERA AFECTADA POR EL FACTOR DE REDUCCION (Fr), QUE SE CONSIDERARA IGUAL A 0.7 PARA LAS COLUMNAS CORTAS Y DE 0.6 PARA LAS COLUMNAS LARGAS

PROPORCIONAMIENTOS RECOMENDADOS PARA MORTERO EN ELEMENTOS ESTRUCTURALES (GDF,

2002a)TIPO DE MORTER

O

PARTES DE

CEMENTO

PARTES DE

CEMENTO DE

PARTES DE CAL

PARTES DE

ARENA

RESISTENCIA A

LA COMPRE

Page 2: .COLUMNAS TABIQUE(1)

28X35 28.00 35.00 56X56 56.00 56.00

Page 3: .COLUMNAS TABIQUE(1)
Page 4: .COLUMNAS TABIQUE(1)

COLUMNA AISLADA DE TABIQUE

OBRA: C-10C. LERDO # 205 SRA. LILIA MOTA MACIAS

FRACC.: BARRIO DE LA ESTACION FECHA: 15 DE AGOSTO DE 2009AGUASCALIENTES, AGS.

DATOS DE MORTEROH = 3.00 MTS. TIPO = III

ECCION = 56X56 CM. RESISTENCIA = 40.00 KG./CM2L..C. = 56.00 L..L. = 56.00

CAPACIDAD DE CARGAOLUMNA = CORTA P = ### CM2

F.R. = 0.7

P.P. = 1,411.20 CM. P = ###

EL PROPORCIONAMIENTO DEL MORTERO A UTILIZAR SERA EL SIGUIENTE

III 1.00 - 1.00 5.50 40.00

AMPLIACION DE CASA HABITACION

No. DE COLUMNA

:UBICACIO

N:PROPIETA

RIO:

MUNICIPIO RESPONS ING. JORGE LUIS HERNANDEZ

DATOS DE LA COLUMNA

RELACION DE ESBELTEZ

PESO PROPIO DE LA COLUMNA

CAPACIDAD DE CARGA NETA DE LA COLUMNA

TIPO DE MORTER

O

PARTES DE

CEMENTO

PARTES DE

CEMENTO DE

ALBAÑIL

PARTES DE CAL

PARTES DE

ARENA

RESISTENCIA A

LA COMPRE

SION