Date post: | 23-Jun-2015 |
Category: |
Engineering |
Upload: | cesar-enrique-gutierrez-candia |
View: | 172 times |
Download: | 2 times |
1
La gama DET3 y DET4
DET3TD DET3TCDET4TD2 DET4TR2 DET4TC2 DET4TCR2
Paul Swinerd
2
La familia DET3
DET3TD– Probador de tierra con pantalla digital de 2 y 3
polos
DET3TC– Probador de tierra con pantalla digital de 2 y 3
polos con capacidad de ART
3
La familia DET4 DET4TD2
–20kΩ max.
DET4TR2– Versión Recargable DET4TD2
DET4TC2–200kΩ max.–Frecuencia Variable de prueba seleccionable por el
usuario– Capacidad ART –Capacidad sin estacas
DET4TCR2–Versión recargable DET4TC2
4
Características de la Gama DET3 y DET4
DET3TD DET3TC DET4TD/R DET4TC/R2
Output fully compliant with IEC 61010-1 and IEC 61557-5 Voltmeter function Noise rejection 40V pk to pk IP54 rating CATIV 100V safety rating Auto check of C and P spike resistance, earth noise V and blown fuse 2 and 3 pole testing without terminal links ART testing capability Ground current measuring capability Stakeless testing capability Variable test frequency 200kΩ max range
5
Qué hacen?
Medir la resistividad del terreno• Elegir la ubicación y el diseño para el sistema de tierra
Medir la resistencia del sistema de Tierra• Comprobar la resistencia suficientemente baja
6
Por qué?1. Elegir la ubicación y el diseño para el sistema de la tierra?
• Encuentra la más baja resistencia posible en un área.• Obtener los valores necesarios para diseñar el sistema de
tierra. – Tamaño del sistema de tierra?– Tipo de sistema de tierra?
• Factores que afectan la resistividad del terreno.– composición del suelo.– La humedad en el suelo.– Temperatura
• Considerar– La resistividad varía a través del año.– La humedad más constante en el vector del agua.– La Temperatura estable por debajo de la línea de
congelación.
7
Por qué?
2. Comprobar si la resistencia del sistema de tierra es lo suficientemente baja?• Permitir que los dispositivos de protección para operar
con la suficiente antelación.• Reducir potenciales incrementos de tierra (GPR)• Danger of shock from GPR (during fault)
– Paso potencial.– Toque potencial.– Conductores adyacentes.
8
¿Qué sistemas de tierra se ponen a prueba?Sistemas de puesta a tierra eléctrica primaria y secundaria.Electrodos de tierra del poste de la red pública.Sistemas de protección contra rayos.Electrodos de tierra Residenciales.Puesta a tierra de seguridad de Maquinaria.Puesta a tierra de sistemas de Informática y comunicaciones.Sistemas de Tierra de EMI / RFI Antena y demás tierras de pedestal.Instalaciones de redes / sistemas de tierra.Sistemas de Tierra CATV .
9
¿Quién los utiliza?
Servicios públicos de energía.Contratistas eléctricos/ electricistas.El personal de mantenimiento de plantas industriales.Las compañías de telecomunicaciones y comunicación de datos.Compañías de pruebas eléctricas.Personal de Servicio de campo y mantenimiento.Compañías petroquímicas.Compañías especialistas de puesta a tierra.Consultores especializados de puesta a tierra.Ferrocarriles.Constructores / instaladores de protección contra rayos.
10
¿Cuáles son las diez mejores características?
DET3TD DET3TC DET4TD/R DET4TC/R2
1 Output fully specified to demonstrate compliance with IEC 61010-1 and IEC 61557-5 2 Voltmeter function 3 Noise rejection 40V pk to pk 4 IP54 rating 5 CATIV 100V safety rating 6 ART testing capability 7 Stakeless testing capability 8 Variable test frequency 9 Ground current measuring capability
10 200kΩ max range
11
1. Salida completamente especifica para demostrarcumplimiento de IEC 61010-1 e IEC 61557-5
Salida especificada como.–25V rms en 0.45mA o 4.5mA–50V rms at 0.45mA
Megger especifica corriente de prueba real - ¿por qué?–0.45mA es lo max. permitido para tensiones de ensayo 33V
para cumplir con la norma de seguridad IEC 61010-1.–25V max. permitido cumpliendo con la norma IEC 61557-5
para instrumento en lugares agrícolas.–4,5 mA máximo en 25 V elegida para dar la vida máxima de
la batería y aún permitir que la precisión con una resolución de 0.01 W y altas resistencias pico.
12
Salida completamente especificada para demostrar el cumplimiento con la norma IEC 61010-1 y IEC 61557-5.
0
10
20
30
40
50
60
70
80
1 2 3 4 5 6 7 8 9 10
mA
V
IEC 61010-1 Normal Condition
NORMAL CONDITION
70V DC, CURRENT LIMITED TO 2mA
NORMAL CONDITION
46.7V PEAK, CURRENT LIMITED TO 0.7mA
(For non-sinusoidal waveforms)
NORMAL CONDITION
33V rms, CURRENT LIMITED TO 0.5mA
INSTRUMENT OUTPUT
25V rms at 0.45mA or 4.5mA rms
50V rms at 0.45mA rms
0
10
20
30
40
50
60
70
80
1 2 3 4 5 6 7 8 9 10
mA
V
IEC 61010-1 Normal Condition
NORMAL CONDITION
70V DC, CURRENT LIMITED TO 2mA
NORMAL CONDITION
46.7V PEAK, CURRENT LIMITED TO 0.7mA
(For non-sinusoidal waveforms)
NORMAL CONDITION
33V rms, CURRENT LIMITED TO 0.5mA
INSTRUMENT OUTPUT
25V rms at 0.45mA or 4.5mA rms
50V rms at 0.45mA rms
0
10
20
30
40
50
60
70
80
1 2 3 4 5 6 7 8 9 10
mAV
SINGLE FAULT CONDITION, AGRICULTURAL LOCATION
25V rms, CURRENT LIMITED TO 3mA rms
SINGLE FAULT CONDITION AGRICULTURAL
LOCATION
35V rms, CURRENT LIMITED TO 5mA peak
For non-sinusoidal waveform
INSTRUMENT OUTPUT
25V rms at 0.45mA or 4.5mA rms
50V rms at 0.45mA rms
IEC 61557-5 Normal condition, Agricultural location
0
10
20
30
40
50
60
70
80
1 2 3 4 5 6 7 8 9 10
mAV
SINGLE FAULT CONDITION, AGRICULTURAL LOCATION
25V rms, CURRENT LIMITED TO 3mA rms
SINGLE FAULT CONDITION AGRICULTURAL
LOCATION
35V rms, CURRENT LIMITED TO 5mA peak
For non-sinusoidal waveform
INSTRUMENT OUTPUT
25V rms at 0.45mA or 4.5mA rms
50V rms at 0.45mA rms
IEC 61557-5 Normal condition, Agricultural location
13
2. Función de voltímetro.
Rango de voltaje seleccionable de hasta 100V.–Característica de seguridad adicional.–Medidas de tensión entre los terminales P1 y P2.–Permite al cliente comprobar si existe potencial de
contacto o de paso antes de desconectar electrodos.
14
3. Rechazo de Ruido de 40 V pico a pico.
Se puede probar dentro de un estado de precisión con hasta 40V pico a pico entre los terminales P1 y P2.Indicador de ruido que avisa cuando el límite es superado.Permite probar en ambientes ruidosos, tales como subestaciones de alta tensión.
15
4. Clasificación IP54
IP = Protección de entrada.5 =Protección de la cantidad de polvo que pudiera interferir con la operación del equipo..4 = medio - Protección contra salpicaduras de agua (lluvia).
16
5. Clasificación de seguridad CATIV 100V
Protegido contra impulsos de 2.500 V de altaenergía.CATIV en ambientes externos.
17
Los cinco siguientes agregados con un DET4TC2 o DET4TCR2
18
6. Mediciones selectivas de‘ART’ (también para el DET3TC)
Técnica de la Varillad Adosada .No hay necesidad de que el electrodo de tierra se desconecte.Utiliza la pinza de corriente 'ICLAMP' para medir la corriente que circula por el electrodo bajo prueba.
19
La mejor aplicación del ART
Tierra en Campo / Tierra en Granjas.Transformadores montados en poste.Sistemas TT independientes (electrodo de tierra).Líneas tensoras Individuales en torres (aislado).Electrodos de protección contra rayos.
20
7. Mediciones "sin estacas".
No hay necesidad de que el electrodo de tierra se desconecte.No hay necesidad de estacas de prueba para su uso.
21
Metodología con Pinza / sin estacas
GroundElectrode
Under Test
Building earth connection/s
ICLAMP
VCLAMP
22
Metodología con Pinza / sin estacas
ICLAMP
VCLAMP
R testR1R2R3R425 Ohms 22 Ohms 19 Ohms 25 Ohms 45 Ohms
R Meas.= 50.6 Ohms
R Meas. = R test + 1 / (1/R1 + 1/R2 + 1/R3 + 1/R4)
23
Metodología con Pinza / sin estacas - Ventajas
La Prueba es rápida y fácil.• No se desconecta la varilla de tierra del sistema.• No hay sondas que necesitan accionarse / ni cables conectados.
Incluye la unión y la resistencia de la conexión en general.• No está disponible con caída del potencial.
.
24
La mejor aplicación de las pruebas "sin estacas".
Tierra en Campo / Tierra en Granjas.Transformadores montados en poste.Línea de Poste de tipo transformador montado cuando está conectado al sistema de Tierra.Puesta a tierra de cable en sótanos de Sub-estación.
• A menudo es imposible conducir en estacas de prueba por lo que esta es una aplicación ideal para la medición sin estacas.
Líneas tensoras Individuales en torres .Electrodos de protección contra rayos.
25
8. Frecuencia de prueba variable
Frecuencias de prueba seleccionables por el usuario (94Hz, 105Hz, 111Hz, y 128Hz)Permite al usuario mover la frecuencia de prueba fuera de la interferencia de la frecuencia de ruido.
26
9. Medición de la corriente de tierra(también para DET3TC)
Utiliza ICLAMP para medir la corriente que fluye.Más conveniente que una medición de tensión de paso.Se sabe exactamente lo que está fluyendo en el electrodo individual.Le indicará si el equipo está defectuoso.Competencia?
–Ninguna …….
27
10. 200kΩ de rango máximo
Ideal para las pruebas de resistencia de tierra en suelos arenosos, rocosos y secos.
Apagado si se muestra alta tolerancia de resistencia pico.
• 200kΩ max• Excelente para el método de punta floja.
28
Conclusión
Mensaje General :“La gama DET3 / 4 ofrece la mejor especificación
general y paquete diseñado específicamente para aplicaciones de la vida real”
–El estuche de transporte es ideal para mantener el instrumento fuera del suelo.
–Tapa que ofrece protección al instrumento e instrucciones.
–Caja de Goma blindada IP54.–Controles y terminales con código de color claros.